RX 10 TOP

Global RX 10 TOP

  GLOBAL RX 10 TOP
Air Volume 160-1600m³/h 
45-440l/s
Inspection side R/L
Counterflow heat exchanger -
Rotary heat exchanger
Pre filter G4
Filter Class (supply  / extract) F7/M5(F7)
Filter kit replacement article number 510118
Filter type  Bag
Filter size in mm (Supply air) 720 x 460 x 380
Filter size in mm (Extract air) 378 x 532 x 360
Free cooling
External pre- / post heating  or cooling (Water/DX)
Internal max post heater
Post heating capacity 21°C 2,91kW
External dampers
Power connection 230 V, 50 Hz, 16A
maximum current without accessories 12A
Motorization Variable speed drive
Heat exchanger STANDARD efficiency D.B. (EN 308)* 78%
Heat exchanger HIGH efficiency D.B. (EN 308)* 82%
Casing radiated sound power level    (LWA) in dB(A) 52,3
SFP (kW/m³/s) at reference air volume* <2
Weight without accessories  365kg
Duct connection (mm) Ø315
Unit size (L x W x H) 1680 x 885 x 1465

* Reference air flow is 70% of maximum air flow with 100Pa external pressure drop